OXYGEN CONTROL DOSING PUMP
Dosing pumps are added next, the dosing point is
very important, With Oxygen Scavengers it can take several
tens of seconds to react depending on the temperature of the feed water so
injecting as soon as possible after
the exit of the feed tank is one ideal point. Dosing directly into the feed tank
is not such a good idea as the
chemical will react with the residual oxygen (from the make up) before it is
driven off by the heat of the hot well's
temperature, there will also be some reaction with the chemical at the surface
of the water.
(Note the injection point).
The configure menu allows for the oxygen pump allows the following pump characteristics to be set:
And for the chemical
Copyright Aquanet International Ltd 2009