The first press of the "Next"  button adds the boiler to the page.

DO NOT CHANGE ANY OF THE BOILER CONDITIONS WHEN BUILDING THE SYSTEM.
THE PROGRAM DOES NOT ALLOW THIS. BUILDING THE SYSTEM IS AN EDUCATIONAL
PROCESS ONLY.
Target levels shown in the in this program where appropriate are broadly in line with BS2486.

Notice the screen has grey and white text areas, the grey areas are calculation results filled in as the once the program
is running a simulation

The boiler steaming rate can be changed from the drop down box and when changed the boiler volume will also change,
the target TDS defaults to 3500mg/l and the boiler pressure when changed will look up the steam tables and fill in the
expected water temperature for that pressure.

The efficiency of the boiler has a marked effect on cost and the program defaults to 80% but this is only a nominal figure and boilers
are available with much higher efficiencies.

The boiler model defaults to Automatic blowdown of the boiler water. Three bottom blows per day of 5 seconds each are the default.
Changing these times have an effect on the boiler operation.

The cost of fuel can be input the cost is either price per Kg for fuel oil or price per cubic Metre for gas, the configuration of the
boiler (Configure menu) allows for the calorific value of the fuel to be entered (typical figures 39Mj/M3 for gas and 43MJ/Kg for Oil)

<< Back    Next>>