TDS Controller for Steam Raising Plant to
5000kg/hr
DESCRIPTION
At a pre-determined interval the controller pulses its scum line
blow down valve and measures the temperature and conductivity of
the discharged boiler water.
If the conductivity is above the pre-set limit it will pulse the
valve
open and closed for a few seconds at a time until the
conductivity
(and hence TDS) falls to within limits, after which it waits for
a
predetermined time until the cycle starts again.
The primary functions are: -
- Surface blow down control
- Optional timed bottom blow down
- Pulsed output control for steam valve
The bottom blow down valve and the steam header valve inputs
have provision for micro-switch feedback which indicate to the
controller the success or failure of the valve opening.
The front panel houses
- LCD display
- Status LEDs
- Alarm / Fault LEDs
- When a valve fails the alarm LED is illuminated.
| SPECIFICATIONS
Input power
110/220VAC 50/60Hz
Power requirement 50 watts
Alarm relay contacts
220Vac @ 1 Amp
Probe energisation
200mV volts
Standard range 0-6000 uMhos
(other ranges available)
Temperature compensation range
0 to 200?C
|
CONTROLS
- Conductivity Set point
- Surface blowdown On Time in seconds
- Surface blowdown Off time in minutes
- Bottom blowdown Period (in minutes)
- Bottom blowdown On time (Max)
- Steam header Valve POP ON time in seconds
- Steam header Valve POP OFF time in seconds
- Alarm band in uMhos
Amplifier Enclosure Material Steel
Rating IP 65
Dimensions 300 x 200 x 120mm
|
|