Aquanet AQ300 LP
 |
Features and
Benefits
- Keeps boilers
scale and corrosion free
- Lower operating
costs
- Ensures correct
chemical levels at all times
- Reduced man hours
in system operation and tests
- Easily
reconfigured for new chemical suppliers = free
choice
Download PDF of
specifications here
|
esigned for industrial steam boiler installations up to 100
bar, the AQ300 accurately monitors the boiler and feed water
conditions. It injects exactly the required amount of chemicals
and provides auto surface blow down control. It keeps the entire
plant within the desired chemical limits, 24 hours a day,
regardless of load.
The units can be fitted with a mixture of pumps of pumps and
programmed for different pressure boilers and water treatment
chemicals.
The system includes pH, conductivity, dissolved oxygen,
temperature probes, data commumications unit with software, feed
flow meters, auto blow down valves, test kit and dosing pumps
complete with suction assemblies and low level alarms.
The software provides for continuous display of all important
readings and pre-formatted ?Management Reports? which outputs a
summary of average readings for any period requested. The unit
can be linked to other AQUANET systems and all readings are
displayed on one monitor. The system is pre-configured for each
installation and a choice of coolers, pumps, flow meters and
blow down valves are available depending on requirements.
Installation can be carried out by the owners staff,
sub-contractor or AQUANET personnel.
Specifications
Dimensions (W) x (H) x (D) mm
1020 x 490 x 250
(assembled c/w chemical drums)
The instrumentation is housed in a split steel
cabinet with hinged lockable doors
The left hand section constructed of stainless steel,
houses the sampling system and probes
The right hand section houses signal conditioning,
control and the communications interface. |
Probes
pH :Range 0 ? 14pH
Automatic temperature compensation
Sealed Reference cell
Resolution 0.5% FSD
Conductitv :Range0-600 Mhos
(other ranges available)
Automatic temperature compensation
Resolution 0.5% FSD
Dissolved Oxygen :Range 2.5 mg/l
Automatic temperature compensation
Resolution 0.5% FSD
Feed Temperature
Stainless steel pocketed probe
0-110?C scaled as 4-20 mA signal |
Flowmeters
Mechanical to suit pipe work.
OR
Ultrasonic Flow Meters (Non penetrating).
Clamps onto outside of existing pipe work.
Transducer maximum operating temperature 130?C
Blowdown Valves
Mechanically operated to 32 bar
Or
Pneumatic,
Rated 100 bar to suit application
Chemical dosing pumps
Air operated 1 litre/hr max 16 bar (max) tefloncoted
Electrically operated diaphragm pump1 litre/hr into 16 bar (max) |
Additional standard features Flushing water system with flow monitoring. Dosing pump manual speed control Dosing pump vent system, returns chemical to drum (No spillage) Fuse failure alarms Auto probe calibration on the unit |
|